露点温度法测定气体燃料中蒸汽含量的试验方法

点击次数:3641 发布时间:2009-06-04

标准号:D1142-95
标准全称应该翻译为:“露点温度法测定气体燃料中蒸汽含量的试验方法”
ASTM D1142 - 95(2006) Standard Test Method for Water Vapor Content of Gaseous Fuels by Measurement of Dew-Point Temperature
Significance and Use

Generally, contracts governing the pipeline transmission of natural gas contain specifications 

limiting the maximum concentration of water vapor allowed. Excess water vapor can cause 

corrosive conditions, degrading pipelines and equipment. It can also condense and freeze or form

 methane hydrates causing blockages. Water-vapor content also affects the heating value of natural gas, thus influencing the quality of the gas. 

This test method permits the determination of water content of natural gas.

1. Scope
1.1 This test method covers the determination of the water vapor content of gaseous fuels by measurement of the dew-point temperature and the calculation therefrom of the water vapor content. Note 1Some gaseous 

fuels contain vapors of hydrocarbons or other components that easily condense into liquid and 

sometimes interfere with or mask the water dew point. When this occurs, it is sometimes very 

helpful to supplement the apparatus in with an optical attachment that uniformly illuminates the dew point mirror and also magnifies the condensate on the mirror. With this attachment it is possible, 

in some cases, to observe separate condensation points of water vapor, hydrocarbons, and 

glycolamines as well as ice points. However, if the dew point of the condensable hydrocarbons is 

higher than the water vapor dew point, when such hydrocarbons are present in large amounts, they 

may flood the mirror and obscure or wash off the water dew point. Best results in distinguishing 

multiple component dew points are obtained when they are not too closely spaced.
Note 2
Condensation of water vapor on the dew-point mirror may appear as liquid water at temperatures as low as 0 to 10F (18 to 23C). At lower

 temperatures an ice point rather than a water dew point likely will be observed. The minimum dew 

point of any vapor that can be observed is limited by the mechanical parts of the equipment. Mirror 

temperatures as low as 150F (100C) have been measured, using liquid nitrogen as the coolant 

with a thermocouple attached to the mirror, instead of a thermometer well. 

 